Chapter 10: Troubleshooting Page 209
032 - Flow Max - Main Flow
Figure 173: Warning 032 -FM Main Flow
This alarm appears at the submaster whenever the measured flow
is more than the Main Line Break Limit established at the
submaster. It indicates that the sum of water from all Flow Max
participants exceeds the Main Line Break Limit. The submaster
automatically issues a STOP WATER warning to all
participants, to insure that all irrigation at every satellite
terminates. The NORMALLY OPEN MV terminal will be
automatically energized at the submaster as well as at the shared
location. IMPORTANT: All future scheduled irrigation for any
of the Flow Max participants will not occur until this alarm has
been cleared at the satellite.
"SAT=" lists the address(es) of any satellites which were
irrigating at the time of the warning.
Example:
Assume a submaster address of 01-00. If the warning
reads "SAT =2,5 GPM=620" THEN satellites 01-02, 01-
05 had irrigating stations and the sum of their measured
flow was 620 GPM.
Action:
Step 1 Review the warnings at the listed satellites to
determine which stations were on at the time of the
warning.
Determine if any of these stations were responsible
for the Main Line Limit failure.
Step 2 Inspect the main line as well as major branches for
failure.
WARNING = FM MAIN FLOW 06/14/96 10:45AM
SAT=2, 5, |¾||½|