Rain Master Irrigation Systems DX2 User Manual
Appendix B: Current Monitor Page 263
situation, the limit checked by the controller is the sum of the
individual station current limits.
Maximum Controller Current
The maximum rated current for any station or combination of
stations is 2.0 Amps. If four devices (field valve solenoid,
Master Valve, Pump, Relay, etc.) that each have current draw of
.50 Amps were on simultaneously, the current would be 2.0
Amps. This is equal to the maximum controller allowance.
Monitor individual station currents and program your stations
accordingly. If you are using older solenoids which draw more
than .50 Amps each, you may consider replacing them.
The controller protects itself in the event that the solenoids draw
more than the maximum allowable current. The associated
station will shut down and the following message will be
displayed:
Figure 194: Short Circuit Warning
For further details on short circuit warning, refer to Chapter 10.
In addition to the built-in short circuit protection, a separate 24
VAC fuse exists (located on the Master Valve/Pump/Power
Assembly board).
In the rare event that the 24 VAC fuse should blow, the
controller has intelligence to detect the blown fuse and inform
the operator with the following message:
Figure 195: Fuse Display Message
WARNING = SHORT CIRCUIT 06/20/96 05:15 PM
STA = PUMP, MV1, 1 |½|
CHECK 24 VAC FUSE