Rain Master Irrigation Systems DX2 User Manual
Appendix B: Current Monitor Page 261
Step 3 Select F1=CURRENT LIMIT. The following screen
is displayed:
Figure 191: Current Limit Entry
The Station Number is displayed with a Max
Current value. If a Master Valve/Pump was entered,
it will be indicated as such in the station number
area.
Step 4 Enter the maximum current limit in Amps then press
ENTER. The limit must be between 0 (zero) and 1.0
Amps. The default maximum limit is 1.0 Amps.
The controller compares the station's AC current
consumption to the station maximum limit. If, after
the station is turned on, the measured current
consumption is larger than the limit, an error
condition is detected.
The suggested maximum current limit is 20% above
normal operating current consumption.
Step 5 Enter the minimum current limit in Amps. The limit
must be between 0 (zero) and 1.0 Amps. The default
minimum current limit is 0.05 Amps.
The controller compares the station's AC current
consumption to the station minimum limit. If, after
the station is turned on, the measured current
consumption is less than the limit, an error condition
is detected.
A value of 0 (zero) indicates the station is not
checked for minimum current violations.
The suggested minimum current limit is 50% of the
normal operating current consumption.
Enter a relatively small, non-zero minimum limit to
detect an open or broken wire. Press ENTER.
STATION # # MAX CURRENT LIMIT: 1.00
ENTER LIMIT ( 0.0 – 1.0 AMPS ) |½|